Home / Voltage Transformers for Measurement

Instrument Transformer Fundamentals

Voltage Transformers for Measurement

Define primary and secondary rated voltages, connection, accuracy and burden for the measurement circuit.

A measurement voltage transformer supplies a scaled voltage to meters or protective relays. Specify the instrument circuit separately from the power transformer's load rating.

Distinguish measurement and power duties

An instrument voltage transformer reproduces the primary voltage within its specified accuracy limits for an instrument circuit. A distribution transformer supplies the energy demanded by downstream loads. State the intended duty first so the supplier can select the right equipment class.

Equipment dutyPurposeMain specification focus
Measurement voltage transformerScaled signal for a meter or relayRatio, accuracy, burden and insulation
Distribution transformerSupplies energy to downstream loadsCapacity, load, primary and secondary voltage
Circuit interfaceConnects the instrument circuitConnection, grounding and approved protection

Read the ratio on the correct voltage basis

An illustrative 12,000:120 V ratio is 100:1. Under the ideal ratio, 11,400 V on the primary gives 114 V on the secondary. Confirm whether each rated voltage is line-to-line or phase-to-neutral, and use the specified connection instead of assuming a conversion between them.

Ideal voltage transformer ratio example: 12,000:120 V scales 11,400 V to 114 V.
Illustrative potential transformer ratio and measured secondary voltage.

Example — ideal voltage transformation

Primary : secondary = 12,000 : 120 = 100 : 1

11,400 V primary → 114 V secondary

Use rated voltage basis and the specified winding connection. Actual accuracy and operating limits are defined by the equipment specification.

Define the measurement interface

List the connected meters and relays, their burden, lead arrangement, required accuracy and insulation level. Include the protection and grounding arrangement on the approved drawing. Review fuse selection and secondary-circuit protection against the equipment instructions.

Drawing and protection record

Record primary and secondary voltage basis, phase connection, terminal identification, burden, accuracy requirement, insulation level, grounding and protective devices on the approved measurement-circuit drawing.

Frequently Asked Questions

What is another name for this device?

Potential transformer is commonly used for an instrument voltage transformer. Match terminology to the equipment specification.

Does the ratio define the complete specification?

Add accuracy, burden, insulation, frequency, connection and installation details.

Prepare a voltage measurement specification

Share the primary and secondary voltage basis, connection, accuracy, burden, insulation, frequency, instrument list and approved protection drawing.