Home / Resources / Electrical Impedance in Transformer Selection

Transformer Technical Guide

Electrical Impedance in Transformer Selection

Read percentage impedance, work through a fault-current example, and collect the right study inputs.

Electrical impedance describes how an AC circuit opposes current. It combines resistance and reactance, so both magnitude and phase matter. In a transformer specification, percentage impedance is a particularly useful value for reviewing voltage performance, fault-current studies and the coordination of connected equipment.

Distinguish resistance from reactance

Resistance represents the component associated with real power loss. Reactance represents the effect of energy storage in magnetic or electric fields. For sinusoidal steady-state analysis, impedance is written as Z = R + jX, where R and X are measured in ohms. For R = 3 ohms and X = 4 ohms, the magnitude is 5 ohms. A 100 V RMS supply across that impedance produces 20 A RMS. The phase relationship still matters when calculating power.

Read the transformer's percentage impedance

Use the value supplied for the actual transformer, together with its kVA base, winding voltages, tap and test conditions. Percentage impedance is related to the proportion of rated voltage required to circulate rated current in the specified short-circuit test. Keep a nameplate photograph and the manufacturer's test report together. Values from different equipment must be placed on consistent bases before they are combined in a study.

Work through a three-phase example

Consider an illustrative 1,000 kVA, 480 V line-to-line transformer with 5% impedance. Its rated secondary current is 1,000,000 divided by (1.732 times 480), approximately 1,203 A. With an infinite upstream source, nominal voltage, a three-phase bolted fault at the secondary terminals, and no motor contribution or impedance-tolerance adjustment, the estimate is 1,203 divided by 0.05, approximately 24.1 kA symmetrical RMS.

Input or resultValueMeaning
Transformer rating1,000 kVAThree-phase nameplate base for this example
Secondary voltage480 VLine-to-line RMS
Impedance5% = 0.05 per unitOn the transformer rating base
Rated currentApproximately 1,203 A1,000,000 / (1.732 x 480)
Terminal fault currentApproximately 24.1 kA1,203 / 0.05 under the stated assumptions
Transformer fault-current example with 1000 kVA, 480 volts and 5 percent impedance
Calculation example using transformer impedance and an ideal upstream source.

Prepare the network study and impedance data sheet

For an installation study, provide the utility source information, transformer test data, cable lengths and characteristics, and connected sources or motors. Include operating arrangements and the specified tolerances. These inputs affect the current available at each fault location. The engineer uses the resulting study to check protective-device duties and equipment ratings at the relevant locations.

Attach the impedance value to a specific transformer and winding base. A useful record identifies the rated kVA, winding voltage, tap position, reference temperature and the source of the value. If a test report gives load loss as well as impedance, retain both for the engineer who determines the resistive and reactive components.

Data fieldExample recordWhy it matters
Equipment IDT1Connects the value to the correct drawing
Rating base1,000 kVADefines the per-unit base
Voltage base480 V line-to-lineIdentifies the winding used in the calculation
Impedance5% on the stated baseEnters the fault-current model
Source impedanceUtility study inputAdds the upstream network contribution
Downstream circuitCable size, material and route lengthEstablishes impedance to the fault location

For the example above, the three-phase base impedance is Zbase = VLL² / S = 480² / 1,000,000 = 0.2304 ohm. A 5% value therefore corresponds to 0.01152 ohm on this secondary base. Keep the complex impedance components and X/R information with the full study.

For step-by-step R, L and C calculations, use the impedance formula examples.

Compare replacement and parallel-operation data

When replacing a transformer, compare its impedance and rating information with the existing study and connected equipment. If transformers will operate in parallel, send the complete data for each unit, including ratio, tap, phase sequence and phase displacement. Ask the project engineer to review load sharing and protection coordination before procurement is finalized.

FAQ

Can I use the example current as a project equipment rating?

Use the completed project short-circuit study, with the actual source, transformer and circuit data, for equipment selection.

Which impedance details belong in an enquiry?

Include the required percentage impedance, rating base, applicable specification and the intended operating arrangement.

Provide the required impedance

Send capacity, winding voltages, impedance and system-study requirements with your transformer enquiry.

Send Transformer Specifications